Items | LX3V-4DA |
Dielectric withstand voltage | 500VAC, 1min (between all terminals and ground) |
Analog circuits | 24V DC ± 10%, 55mA |
(external power supply from main unit) |
Digital circuits | 5V DC, 30mA (internal power supply from main unit) |
Voltage/Current Input | Either voltage or current input can be selected with your choice of input terminal. |
Up to four input points can be used at one time. |
Analog output range | DC -10V to +10V (input resistance: 200kΩ). |
Warning: this unit may be damaged by input voltage in excess of ±15V DC -20mA to +20mA (input resistance:250Ω). |
Warning: this unit may be damaged by input currents in excess of ±32mA. |
Digital input | 12-bit conversion stored in 16-bit 2’s complement form |
Maximum value: +2047 Minimum value: -2048 |
Resolution | 5mV (10V default range 1/2000)/20µA (20mA default range 1/1000) |
Over all accuracy | ±1% (for the range of -10V to +10V)/±1% (for the range of -20mA to +20mA) |
Conversion speed | 15ms/channel (Normal speed), 6ms/channel (High speed) |
CE Certification | CE marked |