BD Module:LX3V-2PT2DAI-BD/LX3V-2PT2DAV-BD

2 * Thermal Resistance Input;

2 * Analog Output (4~20mA)


2 * Thermal Resistance Input; 

2 * Analog Voltage Output(-10v-10v)


Software&manual Inquiry
Specification
ItemLX3V-2PT2DAI-BDLX3V-2PT2DAV-BD
Power supply24VDC±10%50mA; 5VDC±10%, 70mA (Powered by PLC host)5VDC±10%, 70mA (Powered by PLC host)
Temperature input (PT)
Analog input signalPT100 sensor, 3 wires, 2 channels (CH1, CH2)
Sensor current1mA sensor: 100Ω(PT100)
Compensation range-100  - 600 
Digital output-1000 – 6000 (Unit: 0.1 )
12 bits total, 11 bits for data and 1 bit for sign
Accuracy0.2  - 0.3 
Overall accuracy±0.5%
Conversion rate50ms
Conversion characteristicsimage.png
Analog output (DAI)Analog output (DAV)
Rated range4~20mA: 0~2000-10V~10V: -2000~2000
Analog outputDC 4~20mA (the external load resistance is no less than 500Ω)DC-10V~10V (the external load resistance is no less than 2KΩ)
Digital output12 bit binary
Resolution8uA[4~20mA / 2000]5mV[10V default scope 1/2000]
Precision±0.5% of full scale
AD conversion timeOne PLC scanning cycle
Input characteristics

The external load is 250Ω and 0-2000 is converted to 4-20mA



image.png

image.png
InsulationNo insulation in each PLC channel
Occupied pointsNone