BD Module:LX3V-2PT2ADV-BD

2 * Thermal Resistance Input; 

2 * Analog Voltage input(-10v-10v)


Software&manual Inquiry
Specification



ItemLX3V-2PT2ADV-BD
Power supply5VDC±10%, 70mA (Powered by PLC host)
Temperature input (PT)
Analog input signalPT100 sensor, 3 wires, 2 channels (CH1, CH2)
Sensor current1mA sensor: 100Ω(PT100)
Compensation range-100  - 600 
Digital output-1000 – 6000 (Unit: 0.1 )
12 bits total, 11 bits for data and 1 bit for sign
Accuracy0.2  - 0.3 
Overall accuracy±1%
Conversion rate50ms
Conversion characteristicsimage.png
Analog input (ADV)
Analog input rangeDC-10V~10V (input resistance 160KΩ). Note: If the input voltage exceeds ±15V, the unit will be damaged.
Rated range-10V~10V: -2000~2000
The maximum display range-2048~2048
Resolution5mV[10V default scope 1/2000]
Precision±0.5% of full scale
AD conversion timeOne PLC scanning cycle
Input characteristicsimage.png
InsulationNo insulation in each PLC channel
Occupied pointsNone