2 * Analog Input/ Analog Output (4~20mA)
2 * Analog Input/ Output (-10V~10V)
Item | LX3V-2ADI2DAI-BD | LX3V-2ADV2DAV-BD | |
Power supply | 24VDC±10%, 50mA; 5VDC±10%, 70mA (Powered by PLC host) | ||
Analog input (ADI) | Analog input (ADV) | ||
Analog input range | DC 4~20mA (input resistance 250KΩ). Absolute maximum input: -2mA, +30mA | DC-10V~10V (input resistance 160KΩ). Note: If the input voltage exceeds ±15V, the unit will be damaged. | |
Rated range | 4~20mA: 0~2000 | -10V~10V: -2000~2000 | |
The maximum display range | -500~2048 | -2048~2048 | |
Resolution | 8uA[4mA ~20mA / 2000 ] | 5mV[10V default scope 1/2000] | |
Precision | ±0.5% of full scale (4~20mA:±0.08mA) | ±0.5% of full scale | |
AD conversion time | One PLC scanning cycle | ||
Input characteristics | |||
Insulation | No insulation in each PLC channel | ||
Occupied points | None | ||
Analog output (DAI) | Analog output (DAV) | ||
Rated range | 4~20mA: 0~2000 | -10V~10V: -2000~2000 | |
Analog output | DC 4~20mA (the external load resistance is no less than 500Ω) | DC-10V~10V (the external load resistance is no less than 2KΩ) | |
Digital output | 12 bit binary | ||
Resolution | 8uA[4~20mA / 2000] | 5mV[10V default scope 1/2000] | |
Precision | ±0.5% of full scale | ||
AD conversion time | One PLC scanning cycle | ||
Input characteristics | The external load is 250Ω and 0-2000 is converted to 4-20mA | ||
Insulation | No insulation in each PLC channel | ||
Occupied points | None |